Local display | With
|
Number or control scheme lines | 120 with ladder programming <= 200 with FBD programming
|
Cycle time | 6...90 ms
|
Backup time | 10 years at 25 °C
|
Clock drift | 6 s/month at 25 °C 12 min/year at 0...55 °C
|
Checks | Program memory on each power up
|
[Us] rated supply voltage | 100...240 V
|
Supply voltage limits | 85...264 V
|
Supply frequency | 50/60 Hz
|
Supply current | 80 mA at 100 V (without extension) 30 mA at 240 V (without extension)
|
Power consumption in VA | 7 VA without extension
|
Isolation voltage | 1780 V
|
Protection type | Against inversion of terminals (control instructions not executed)
|
Discrete input number | 8
|
Discrete input voltage | 100...240 V AC
|
Discrete input current | 0.6 mA
|
Discrete input frequency | 47...53 Hz 57...63 Hz
|
Voltage state1 guaranteed | >= 79 V for discrete input
|
Voltage state 0 guaranteed | <= 40 V for discrete input
|
Current state 1 guaranteed | > 0.17 mA for discrete input
|
Current state 0 guaranteed | < 0.5 mA for discrete input
|
Input impedance | 350 kOhm (discrete input)
|
Number of outputs | 4 relay output(s)
|
Output voltage limits | 24...250 V AC 5...30 V DC (relay output)
|
Contacts type and composition | NO for relay output
|
Output thermal current | 8 A for all 4 outputs (relay output)
|
Electrical durability | 500000 cycles DC-13 at 24 V, 0.6 A for relay output conforming to EN/IEC 60947-5-1 500000 cycles DC-12 at 24 V, 1.5 A for relay output conforming to EN/IEC 60947-5-1 500000 cycles AC-15 at 230 V, 0.9 A for relay output conforming to EN/IEC 60947-5-1 500000 cycles AC-12 at 230 V, 1.5 A for relay output conforming to EN/IEC 60947-5-1
|
Switching capacity in mA | >= 10 mA at 12 V (relay output)
|
Operating rate in Hz | 10 Hz (no load) for relay output 0.1 Hz (at Ie) for relay output
|
Mechanical durability | 10000000 cycles (relay output)
|
[Uimp] rated impulse withstand voltage | 4 kV conforming to EN/IEC 60947-1 and EN/IEC 60664-1
|
Clock | With
|
Response time | 5 ms (from state 1 to state 0) for relay output 10 ms (from state 0 to state 1) for relay output 50...255 ms with FBD programming (from state 1 to state 0) for discrete input 50...255 ms with FBD programming (from state 0 to state 1) for discrete input 50 ms with ladder programming (from state 1 to state 0) for discrete input 50 ms with ladder programming (from state 0 to state 1) for discrete input
|
Connections - terminals | Screw terminals, clamping capacity: 2 x 0.25...2 x 0.75 mm² AWG 24...AWG 18 flexible with cable end Screw terminals, clamping capacity: 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16 solid Screw terminals, clamping capacity: 1 x 0.25...1 x 2.5 mm² AWG 24...AWG 14 flexible with cable end Screw terminals, clamping capacity: 1 x 0.2...1 x 2.5 mm² AWG 25...AWG 14 solid Screw terminals, clamping capacity: 1 x 0.2...1 x 2.5 mm² AWG 25...AWG 14 semi-solid
|
Tightening torque | 0.5 N.m
|
Overvoltage category | III conforming to EN/IEC 60664-1
|
Product weight | 0.25 kg
|