Number or control scheme lines | 120 with ladder programming
|
Cycle time | 6...90 ms
|
Backup time | 10 years at 25 °C
|
Clock drift | 12 min/year at 0...55 °C
|
Checks | Program memory on each power up
|
[Us] rated supply voltage | 24 V DC
|
Supply voltage limits | 19.2...30 V
|
Reverse polarity protection | With
|
Discrete input number | 6 conforming to EN/IEC 61131-2 type 1
|
Discrete input type | Resistive
|
Discrete input voltage | 24 V DC
|
Discrete input current | 4 mA
|
Counting frequency | 1 kHz for discrete input
|
Voltage state1 guaranteed | >= 15 V for IB...IG used as discrete input circuit >= 15 V for I1...IA and IH...IR discrete input circuit
|
Voltage state 0 guaranteed | <= 5 V for IB...IG used as discrete input circuit <= 5 V for I1...IA and IH...IR discrete input circuit
|
Current state 1 guaranteed | >= 2.2 mA for I1...IA and IH...IR discrete input circuit >= 1.2 mA for IB...IG used as discrete input circuit
|
Current state 0 guaranteed | < 0.75 mA for I1...IA and IH...IR discrete input circuit < 0.5 mA for IB...IG used as discrete input circuit
|
Input compatibility | 3-wire proximity sensors PNP (discrete input)
|
Input impedance | 7.4 kOhm (I1...IA and IH...IR discrete input circuit) 12 kOhm (IB...IG used as discrete input circuit)
|
Number of outputs | 4 relay output(s)
|
Output voltage limits | 5...30 V DC (relay output) 24...250 V AC (relay output)
|
Contacts type and composition | NO for relay output
|
Output thermal current | 8 A for all 4 outputs (relay output)
|
Electrical durability | 500000 cycles at 24 V, 1.5 A (DC-12) for relay output conforming to EN/IEC 60947-5-1 500000 cycles at 24 V, 0.6 A (DC-13) for relay output conforming to EN/IEC 60947-5-1 500000 cycles at 230 V, 1.5 A (AC-12) for relay output conforming to EN/IEC 60947-5-1 500000 cycles at 230 V, 0.9 A (AC-15) for relay output conforming to EN/IEC 60947-5-1
|
Switching capacity in mA | >= 10 mA at 12 V (relay output)
|
Operating rate in Hz | 10 Hz (no load) for relay output 0.1 Hz (at Ie) for relay output
|
Mechanical durability | 10000000 cycles (relay output)
|
[Uimp] rated impulse withstand voltage | 4 kV conforming to EN/IEC 60947-1 and EN/IEC 60664-1
|
Response time | 5 ms (from state 1 to state 0) for relay output 10 ms (from state 0 to state 1) for relay output
|
Connections - terminals | Screw terminals, solid cable 2 x 0.2...2 x 1.5 mm² / AWG 24...AWG 16 AWG Screw terminals, solid cable 1 x 0.2...1 x 2.5 mm² / AWG 25...AWG 14 AWG Screw terminals, semi-solid cable 1 x 0.2...1 x 2.5 mm² / AWG 25...AWG 14 AWG Screw terminals, flexible cable with cable end 2 x 0.25...2 x 0.75 mm² / AWG 24...AWG 18 AWG Screw terminals, flexible cable with cable end 1 x 0.25...1 x 2.5 mm² / AWG 24...AWG 14 AWG
|
Tightening torque | 0.5 N.m
|
Overvoltage category | III conforming to EN/IEC 60664-1
|
Product weight | 0.2 kg
|